A test verified model development study for a nuclear water chiller using the seismic qualification analysis and test

4Citations
Citations of this article
5Readers
Mendeley users who have this article in their library.

Abstract

This paper is a study on a nuclear water chiller. It presents a test-verified finite element model of a water chiller to be used at a Nuclear Power Plant. The test-verified model predicts natural frequencies within 5% for all major modes below 50 Hz. This model accurately represents the dynamic characteristics of the actual hardware and is qualified for its use in the final stress analysis for seismic verification.

Cite

CITATION STYLE

APA

Sur, U. (2011). A test verified model development study for a nuclear water chiller using the seismic qualification analysis and test. Nuclear Engineering and Technology, 43(4), 355–360. https://doi.org/10.5516/NET.2011.43.4.355