An optimal design method is proposed in this paper to improve the safety and price competitiveness of floating photovoltaic (PV) systems. From the standards for grounding by the International Electrotechnical Commission (IEC) 60364, the Electrical Equipment Technology Standards (EETS) are set up for the grounding resistance to be less than or equal to 10 W for high voltage (above 750 V DC) and extra high voltage (above 7000 V) systems. In order to satisfy this criterion, a parallel connection of grounding electrodes is essential in the system. Furthermore, inter-electrode interference should be considered to reflect the resistance increase due to the potential increase between electrodes. Therefore, in this study, the parallel grounding resistance according to the distance and number of electrodes, as well as the arrangement method were theoretically predicted and compared with the measured values. For the first time, the design of grounding electrodes has been applied to real floating PV systems and is expected to satisfy EETS.
CITATION STYLE
Bhang, B. G., Kim, G. G., Cha, H. L., Kim, D. K., Choi, J. H., Park, S. Y., & Ahn, H. K. (2018). Design methods of underwater grounding electrode array by considering inter-electrode interference for floating PVs. Energies, 11(4). https://doi.org/10.3390/en11040982