Observer-based sliding mode control to improve stability of three-phase LCL-filtered grid-connected VSIs

18Citations
Citations of this article
12Readers
Mendeley users who have this article in their library.

Abstract

Grid-connected voltage source inverters (VSIs) with LCL filters have been widely used for distributed generation systems (DGs). Various control methods have been studied to achieve good performance. Among them, sliding mode control has been applied to LCL-filtered grid-connected VSIs for its fast, dynamic response and strong robustness. However, LCL networks can easily cause instability problems under weak grid conditions such as grid impedance variation. At the same time, the stability design of sliding mode control applied for LCL-filtered grid-connected inverters are important, but they lack detailed parameters design in recent papers. In this paper, a design of observer-based sliding mode control to improve the stability of three-phase LCL-filtered grid-connected VSIs was proposed. The theoretical stability analysis was developed to consider the effect of the system discretization and grid impedance variations. Finally, a 3-kW, 110-V, 50-Hz experimental setup has been built to demonstrate the validation of the proposed method.

Cite

CITATION STYLE

APA

Huang, M., Li, H., Wu, W., & Blaabjerg, F. (2019). Observer-based sliding mode control to improve stability of three-phase LCL-filtered grid-connected VSIs. Energies, 12(8). https://doi.org/10.3390/en12081421