Cooling tower Legionella pneumophila surveillance results: Vancouver, Canada, 2021

7Citations
Citations of this article
18Readers
Mendeley users who have this article in their library.

Abstract

Cooling towers have been linked to Legionnaires' disease cases and outbreaks. Legionella pneumophila results (from a culture-based method) are presented for 557 cooling towers across the City of Vancouver, Canada for 2021. Results of 10 CFU/mL or greater (defined as exceedances) were reported for 30 cooling towers (5.4%), including six >1,000 CFU/mL, and L. pneumophila serogroup 1 (sg1) was identified in 17 of these cooling towers (out of 28 with serogroup-level analysis). The data indicate highly localised Legionella issues, with exceedances concentrated within 16 facilities, including two hospitals. In the 3 months preceding each cooling tower exceedance, the nearest municipal water sampling station had a free chlorine residual of at least 0.46 mg/L and a temperature of <20 °C. There was not a statistically significant correlation between the L. pneumophila concentration of a cooling tower in exceedance and the municipal water free chlorine residual, temperature, pH, turbidity or conductivity. There was a statistically significant negative correlation between the concentrations of L. pneumophila sg1 and other L. pneumophila serogroups in cooling towers. This unique dataset underscores the pivotal role of building owners and managers in preventing the growth of Legionella bacteria and the value of regulations to verify operations and maintenance practices.

Cite

CITATION STYLE

APA

Radziminski, C., & White, P. (2023). Cooling tower Legionella pneumophila surveillance results: Vancouver, Canada, 2021. Journal of Water and Health, 21(3), 313–328. https://doi.org/10.2166/wh.2023.154

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free