This paper proposes a simple and fast way to determine the direction of a fault in a multi-terminal high voltage direct current (HVDC) grid by comparing the rate of change of voltage (ROCOV) values at either side of the di/dt limiting inductors at the line terminals. A local measurement based secure and fast protection method is implemented by supervising a basic ROCOV relay with a directional element. This directional information is also used to develop a slower communication based DC line protection scheme for detecting high resistance faults. The proposed protection scheme is applied to a multi-level modular converter based three-terminal HVDC grid and its security and sensitivity are evaluated through electromagnetic transient simulations. A methodology to set the protection thresholds considering the constraints imposed by the breaker technology and communication delays is also presented. With properly designed di/dt limiting inductors, the ability of clearing any DC transmission system fault before fault currents exceeds a given breaker capacity is demonstrated.
Author supplied keywords
Cite
CITATION STYLE
Haleem, N. M., & Rajapakse, A. D. (2017). Application of new directional logic to improve DC side fault discrimination for high resistance faults in HVDC grids. Journal of Modern Power Systems and Clean Energy, 5(4), 560–573. https://doi.org/10.1007/s40565-017-0301-4