EMT real-time simulation model of a 2 GW offshore renewable energy hub integrating electrolysers

11Citations
Citations of this article
23Readers
Mendeley users who have this article in their library.

Abstract

Due to their weak nature, such as low inertia, offshore energy hubs are prone to un-precedented fast dynamic phenomena. This can lead to undesired instability problems. Recent literature, with main focus on onshore systems, suggests that electrolysers could be an attractive option to support wind generators in the mitigation of balancing problems. This paper presents an Electromagnetic Transient (EMT) model for real-time simulation based study of the dynamics of active power and voltage responses of offshore hubs due to wind speed fluctuations. The purpose of this study was to ascertain the ability of an electrolyser to support an offshore energy hub under different scenarios and with different locations of the electrolyser. Two locations of Proton Exchange Membrane (PEM) electrolysers were considered: centralised (at the AC common bus of the hub) or distributed (at the DC link of the wind turbines). Numerical simulations conducted in RSCAD® on a 2 GW offshore hub with 4 × 500 MW wind power plants and 330 or 600 MW PEM electrolysers show that electrolysers can effectively support the mitigation of sudden wind speed variations, irrespective of the location. The distributed location of electrolysers can be beneficial to prevent large spillage of wind power generation during the isolation of faults within the hub.

Cite

CITATION STYLE

APA

Marchand, J., Shetgaonkar, A., Torres, J. L. R., Lekic, A., & Palensky, P. (2021). EMT real-time simulation model of a 2 GW offshore renewable energy hub integrating electrolysers. Energies, 14(24). https://doi.org/10.3390/en14248547

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free