Multi-Wavelength Densitometer for Experimental Research on the Optical Characteristics of Smoke Layers

7Citations
Citations of this article
23Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

A novel multi-wavelength densitometer was built for the purpose of continuous and simultaneous measurements of light obscuration in smoke layers, concurrently in five bands (λ = 450 nm, 520 nm, 658 nm, 830 nm and 980 nm). This device was used for determining transmittance and visibility in smoke parameters of a smoke layer from the fire of 1.00 dm3 of n-Heptane in a 0.33 × 0.33 m tray located in a test chamber (9.60 × 9.80 × 4.00 m3). The performance of the device was compared with a commercial Lorenz densitometer at 880 nm. Significant differences in measured value of transmittance were observed between the different sensors – from 65% at 450 nm (blue light), 80% at 658 nm (red light) to 95% at 980 nm (IR). The visibility in smoke, estimated following the theory of Jin for light reflecting signs (K = 3), ranged from 7.5 m (blue light) to 12 m (red light) and for the light-emitting (K = 8) signs from 18 to 32 m, respectively. The performed experiment has confirmed the applicability and added value of multi-wavelength measurements of light-extinction in fire experiments. The device was sensitive to temperature variations and requires active cooling and careful warm-up prior to experiments, to reach the expected sensitivity.

Cite

CITATION STYLE

APA

Węgrzyński, W., Antosiewicz, P., & Fangrat, J. (2021). Multi-Wavelength Densitometer for Experimental Research on the Optical Characteristics of Smoke Layers. Fire Technology, 57(5), 2683–2706. https://doi.org/10.1007/s10694-021-01139-5

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free