Optimal Location and Capacity of the Distributed Energy Storage System in a Distribution Network

26Citations
Citations of this article
24Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

Given the current situation of large-scale energy storage system (ESS) access in distribution network, a practical distributed ESS location and capacity optimization model is proposed. Firstly, a weighted voltage sensitivity is proposed to select the grid-connected node set of ESS. On this basis, the distributed ESS location model is established, which aims at reducing voltage deviation and active power loss of the distribution network. Then, an ESS partition method based on the improved flame propagation model is proposed, and the partition results are obtained by constructing the flammability of nodes, the wind direction of flame propagation, speed of flame propagation and other indicators. Based on partition results, the capacity optimization model is established with the maximum annual net income of energy stored in the partition as the objective function. Finally, the improved IEEE-33 bus distribution network is used to demonstrate the effectiveness and feasibility of the proposed model.

Cite

CITATION STYLE

APA

Tang, X., Deng, K., Wu, Q., & Feng, Y. (2020). Optimal Location and Capacity of the Distributed Energy Storage System in a Distribution Network. IEEE Access, 8, 15576–15585. https://doi.org/10.1109/aCCESS.2020.2967435